-
The minimum horizontal vent length is 3'.
-
If possible, do not terminate the horizontal vent through a
wall that is exposed to prevailing wind. Exposure to excessive
winds can
affect unit performance.
-
Vent termination must be free from obstructions and at least
12" above ground level and maximum snow height.
-
Do not terminate vent directly below roof eaves or above a
walkway, or any other area where condensate dripping may be
troublesome and
may cause some staining. Avoid windows where steam may cause fogging or
ice buildup.
-
When horizontally vented, minimum clearance for termination
from any door, window, gravity air inlet, gas or electric meter,
regulators,
and relief equipment is 4'. In Canada, termination is 6'.
-
Vent termination must be a minimum of 4' below or 4
horizontally from any soffit vent of under-eave on a Mr.Heater or 3' on a
Reznor.
-
Vent must be a minimum of 6' from an inside corner formed by 2
exterior walls. If possible, leave a 10' clearance.
-
Vent termination must be a minimum of 10' from any forced air
inlet (includes fresh air inlet to other appliances, such as a dryer)
-
When termination is routed through an exterior combustible
wall the vent must be supported using a listed clearance thimble.
-
For horizontal venting, the vent pipe shall be supported with
hangers no more the 3' apart to prevent movement after installation.